Due to their compact design, the cable conversion current transformers are particularly suitable for use in hard-to-reach places and in limited space. The split core halves further facilitate installation on the cable or rail. Wherever an interruption of the current path is problematic or a measuring device needs to be easily retrofitted, cable conversion current transformers are the right choice. The secure mounting of the primary cable in the current transformer is constructively ensured and confirmed by a clearly audible click sound. Two included UV-resistant cable ties additionally secure the transformer.
Environmental conditions:
Installation location indoors
Ambient temperatures –10 °C to +55 °C
Storage temperatures –20 °C to +70 °C
Relative humidity 5 % to 85 %, condensation must be excluded
Pollution degree 2
Protection class IP20
Application conditions:
Standard IEC 61869-2:2012
Thermal rated short-time current (Ith) 60 x Ipr/1s
Thermal rated continuous current (Icth) 100 %
Rated insulation level 0.72/3/- kV
Rated frequency 50/60 Hz
Insulation material class E (120 °C)
Housing material PA 6.6, UL94: V2.