Powerwalker AVR 3000/SIV Schuko 3000VA / 2400W automatic voltage regulator
Powerwalker AVR 3000/SIV Schuko 3000VA / 2400W automatic voltage regulator
Is this really an online double converter (protection class 9)? From the information I could find in the internet, it looks like it's not. Why also the other models from Powerwalker AVR Xxx / SIV series are not classified as such? I hoped that I could use this for sensitive audio equipment to reduce issues with the ground loop, but it seems to be not the case.
not usable for your application i guess, in and output are NOT galvanically isolated. (i measured/tested)
its just a transformer with 5 taps that switches automatically to keep the output voltage between 180 and 245V for input voltages between 120 (NOT 110) and 250V input
standby use 15-30W (dependent on V-in), probably an auto-transformer, N-in is directly connected to N-out.