I can't quite underatand how you can plug this in the standard Swiss socket (10 A) ? 230 V * 10 A = 2300 W, no? And this consumes 3500 W
Manual https://whirlpool-cdn.thron.com/static...
I=P/U 3'500W / 230V = 15.2A
The standard swiss socket (Typ 12 and Typ 13) are rated for max 10amps.
Thats one side of the problem. The other one is the to small fuse.
Maybe you want contact direct the Digitec customer service and ask them what would be there solution...
You would need a socket Typ 23, cable with min 3x2.5mm2 and a 16A fuse in the distribution panel. For industrial use a CEE16 socket/plug would be an other option. Therefore i don't see this AC for home use.
- - - - - - - - - - - - - - - - -
https://www.esti.admin.ch/inhalte...
- - - - - - - - - - - - - - - - -
Digitec (or any other Swiss dealer) is obliged to deliver electrical devices with a Swiss plug. If the device comes with a foreign plug, a suitable replacement cable should be supplied if the power cable is pluggable or alternatively, if the power cable is firmly connected, a suitable adapter should be supplied.
If the device comes without a suitable plug, complain to customer service and insist on a cable or adapter, free of charge.
Infos Digitec --> https://helpcenter.digitec.ch/hc...
#1 --> https://www.esti.admin.ch/de...
- - - - - - - - - - - - - - - - -
It consumes 1345 W in cooling mode, this is called power input, see silver sticker on the side.