Circuit breaker 3VA6 UL, frame 600, switching capacity class C, 100 kA at 480 V, 4-pole, plant protection ETU856, LSI, In=600 A, overload protection Ir=240 A to 600 A, short-circuit protection Isd=0.6 to 9x In, Ii=1.5 to 9x In, adjustable neutral conductor protection (OFF, up to 100%), earth fault alarm reporting via EFB300 or COM without connection. Compact circuit breaker 3VA6 with ETU 8 series for plant protection, UL approval. The Siemens 3VA UL compact circuit breakers are an essential component of the SENTRON protection devices for industrial applications as well as for infrastructure applications. They provide effective plant and starter protection through safe disconnection in overload and short-circuit situations. The 3VA UL sets standards in flexibility and modular accessory variety. Furthermore, the compact circuit breaker 3VA UL offers the best conditions for globally exporting machines and switchgear manufacturers. In addition to the IEC standard, both series 3VA5 and 3VA6 also meet the UL standard. All functionalities can thus be used and implemented worldwide for installations. This variant of the compact circuit breaker 3VA is characterized primarily by: 1. Compact design. 2. Available as a variant for plant protection. 3. Available in 3- and 4-pole versions. 4. Four switching capacity classes from 55 kA to 150 kA at 480 V. 5. Depending on the frame size: rated current 40 A to 600 A. 6. Installation possible in fixed installation, plug-in technology, and slide-in technology. 7. The series features an electronic overcurrent release. 8. Equipped with an integrated display for measurement value indication. 9. Integrated measurement function and optional communication connection via Modbus TCP, Modbus RTU, PROFINET, and PROFIBUS. 10. Modular and easy-to-install internal accessories with diverse functions.
Circuit breaker type | Circuit breaker |
number of poles | 4 |
Item number | 34009562 |
Manufacturer | Siemens |
Category | Residual-current device |
Manufacturer no. | 3VA6460-7KT41-0AA0 |
Release date | 17.5.2023 |
Circuit breaker type | Circuit breaker |
number of poles | 4 |
Rated voltage | 690 V |
Rated insulation voltage Ui | 480 V |
Residual current (rated differential current) | 100000 A |
Protection type (IP code) | IP40 |
Country of origin | Czech Republic |
Manufacturer commitment | RE100, SBTi |
Manufacturer compensation | According to RE100, the manufacturer Siemens fully compensates for its energy consumption, leading to a reduction in emissions. |
CO₂-Emission | |
Climate contribution |
Items per sales unit | 1 Piece |
How often does a product of this brand in the «Residual-current device» category have a defect within the first 24 months?
Source: Digitec GalaxusHow many working days on average does it take to process a warranty claim from when it arrives at the service centre until it’s back with the customer?
Source: Digitec GalaxusUnfortunately, we don't have enough data for this category yet.
How often is a product of this brand in the «Residual-current device» category returned?
Source: Digitec Galaxus